Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 08/06/2002 |
PLUMBING - GAS PRESSURE TEST |
|
Approved |
IVRS - Inspection 0000* |
| 08/05/2002 |
PLUMBING - GAS PRESSURE TEST |
|
Denied |
IVRS - Inspection 0999* |
| 08/01/2002 |
PLUMBING - GAS PRESSURE TEST |
|
Denied |
1.) WATER HTR P & T VALVE IS STUCK CLOSED 2.) WATER HTR FLU VENT DBL WALL REQUIRES 1" CLEARANCE AROUND COMBUSTIONABLE MATERIAL 3.) MUST CALCULATE BTU & CFH DEMAND FOR GAS LINE SIZEING. 4.) GAS RANGE HAS 3/4" OUTLET THEN SUPPLY MUST BE 3/4" 5.) WATER HTR ENCLOSURE REQUIRE 2 10 X 10 GRILLS FOR FRESH AIR COMBUSTION RELIEFE 6.) MUST STRAP GAS LINE EVERY 6'-0". 7.) MUST SEAL PENETRATION THRU WALLS. |