Permit: T02PL01389

Parcel: 12705044A


Addresses:

728 N SWAN RD


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T02PL01389

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
08/06/2002 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection 0000*
08/05/2002 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*
08/01/2002 PLUMBING - GAS PRESSURE TEST Denied 1.) WATER HTR P & T VALVE IS STUCK CLOSED 2.) WATER HTR FLU VENT DBL WALL REQUIRES 1" CLEARANCE AROUND COMBUSTIONABLE MATERIAL 3.) MUST CALCULATE BTU & CFH DEMAND FOR GAS LINE SIZEING. 4.) GAS RANGE HAS 3/4" OUTLET THEN SUPPLY MUST BE 3/4" 5.) WATER HTR ENCLOSURE REQUIRE 2 10 X 10 GRILLS FOR FRESH AIR COMBUSTION RELIEFE 6.) MUST STRAP GAS LINE EVERY 6'-0". 7.) MUST SEAL PENETRATION THRU WALLS.