Permit: T02PL01327

Parcel: 132101390

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/16/2002 PLUMBING - FINAL Approved IVRS - Inspection 0000*1.) CORRECTION MADE OK 2.) OK FOR GAS 3.) UCC LEFT AT METER. S.W. GAS 889-1888.
08/15/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) SEE NOTE #2 ABOVE. 2.) THE VALVE IS TO BE IMMEDIATELY UPSTREAM OF THE UNION. YOU HAVE THE UNION FIRST THEN THE VALVE. SWITCH POSITIONS AND RE-TEST.