Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/09/2002 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*PROVIDE AN ENCLOSURE AROUND WATER HEATER. PROVIDE P & T DRAIN LINE ON WATER HEATER. REMOVE THE UNION FROM GAS LINE SUPPLYING WATER HEATER. USE DOUBLE WALL VENT PIPE FOR WATER HEATER EXTENDING MIN. 1" ABOVE ROOF W/AN APPROVED CAP NO T-TOPS ALLOWED USE REVERSE THREAD COUPLING & NIPPLE TO REPLACE UNION RETEST SYSTEM. 2'-3 AMERIVENT 1-AMERIVENT CAP 1 AMERIVENT FLASHING. |
|
| 09/09/2002 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* | |
| 07/18/2002 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*1.) PRESSURE TEST COMPLETE GAS PIPE SYSTEM. 2.) INSTALL APPROVED VENT & VENT CAP. ON WATER HEATER. 3.) REPLACE P & T VALVE IN WATER HEATER. |