Permit: T02PL01162

Parcel: 133102330


Addresses:

8440 E BOGOTA PL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/15/2002 PLUMBING - FINAL Approved IVRS - Inspection 0000*1.) GAS PRESSURE TEST IS OK 2.) GAS SHUT OFF VALVES IS OK 3.) WATER HTR FLU VENT, P & T VALVE & DRAIN IS OK 4.) FURNACE FLU VENT IS OK.
08/14/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) CAN NOT HAVE FLEX CONNECTOR PENETRATE THROUGH HOUSEING OF POOL HTR AS REQUESTED. 2.) MUST STRAP DOWN 3/4" GAS DROP FOR RANGE WITH APPROVED TWO HOLE STRAPS. 3.) MUST PROVIDE A DRAIN VALVE FOR WATER HTR P & T DRAIN. 4.) MUST SCREW DOWN WATER HTR FLU VENT TO APPLIANCE COLLAR WITH (3) SHEET METAL SCREWS 5.) MUST REMOVE OLD GAS VALVE @ WATER HTR & REPLACE WIHT A AGA APPROVED SHUT OFF VALVE.
08/13/2002 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*
06/20/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*FLEX GAS CONNECTOR CANNOT PENETRATE CABINET ON POOL HEATER. USE AGA OR CSA APPROVED SHUT OFF VALVE AT STOVE & POOL HEATER. NEW GAS PIPE NOT HOLDING PRESSURE. NEED TO SEE FINAL CONNECTIONS TO EXISTING PIPE. WHEN CONNECTING NEW PIPE TO EXISTING PIPE IN GARAGE, USE REVERSE THREAD COUPLING & NIPPLE. NO UNIONS.