Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/15/2002 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*1.) GAS PRESSURE TEST IS OK 2.) GAS SHUT OFF VALVES IS OK 3.) WATER HTR FLU VENT, P & T VALVE & DRAIN IS OK 4.) FURNACE FLU VENT IS OK. |
| 08/14/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) CAN NOT HAVE FLEX CONNECTOR PENETRATE THROUGH HOUSEING OF POOL HTR AS REQUESTED. 2.) MUST STRAP DOWN 3/4" GAS DROP FOR RANGE WITH APPROVED TWO HOLE STRAPS. 3.) MUST PROVIDE A DRAIN VALVE FOR WATER HTR P & T DRAIN. 4.) MUST SCREW DOWN WATER HTR FLU VENT TO APPLIANCE COLLAR WITH (3) SHEET METAL SCREWS 5.) MUST REMOVE OLD GAS VALVE @ WATER HTR & REPLACE WIHT A AGA APPROVED SHUT OFF VALVE. |
| 08/13/2002 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 06/20/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*FLEX GAS CONNECTOR CANNOT PENETRATE CABINET ON POOL HEATER. USE AGA OR CSA APPROVED SHUT OFF VALVE AT STOVE & POOL HEATER. NEW GAS PIPE NOT HOLDING PRESSURE. NEED TO SEE FINAL CONNECTIONS TO EXISTING PIPE. WHEN CONNECTING NEW PIPE TO EXISTING PIPE IN GARAGE, USE REVERSE THREAD COUPLING & NIPPLE. NO UNIONS. |