Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/02/2002 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 06/28/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) NO PRESSURE AT GUAGE NEED 10# MINIMUM TEST 2.) WHERE PIPING MEETS, THE CONNECTION SHALL BE MADE WITH A RIGHT LEFT NIPPLE AND COUPLING NO UNIONS UNDERGROUND. 3.) CAP OFF ALL EXISTING PIPING NOT BEING USED. 4.) SECURE PERMIT FOR NEW WATER HEATER. 5.) ALL GAS PIPING TO BE A MINIMUM OF 12" BELOW GRADE. |
| 06/18/2002 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*NOT READY FOR INSPECTION. |