Permit: T02PL01044

Parcel: 127081430


Addresses:

5442 E BURNS ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
05/31/2002 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection 0000*1.) CORRECTIONS MADE OK 2.) OK FOR GAS 3.) UCC LEFT AT METER.
05/29/2002 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*1.) SUPPORT GAS PIPING 1 1/2" OFF OF ROOF, USE APPROVED STRAPS. 2.) USE APPROVED FLASHING WHERE PIPING PENETRATE ROOF 3.) WHERE PIPING MEETS, USE A RIGHT LEFT NIPPLE OF COUPLING. 4.) A GROUND JOINT UNION MAY BE USED IN AN EXTERIOR ACCESSIBLE LOCATION, WHEN PRECEEDED BY AN APPROVED BLDG. SHUT OFF VALVE. 5.) SUPPORT PIPING DROP 6.) ALL VALVES TO BE AGA OR CSA APPROVED.