Inspection Status: Approved
Inspection History: PLUMBING - GAS RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 06/20/2002 |
PLUMBING - GAS RECONNECT |
|
Approved |
IVRS - Inspection 0000* |
| 05/24/2002 |
PLUMBING - GAS RECONNECT |
|
Denied |
IVRS - Inspection 0999*1.) SECURE PERMITS FOR ROOF-TOP UNITS AND NEW WATER HEATERS I CAN NOT RELEASE GAS TO UNAPPROVED APPLIANCES. 2.) REMOVE UNION IN GAS LINE USE RIGHT LEFT NIPPLE AND COUPLING. 3.) ALL VALVES TO BE AGA OR CSA APPROVED. 4.) SUPPORT GAS PIPING ON ROOF 5.) VENT SYSTEM ON WATER HEATER NOT TO CODE. MUST EXTEND 2' ABOVE ROOF WITH FLASHING, STORM COLLAR, AND APPROVED VENT CAP. |