Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESS TEST FNL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/22/2002 |
PLUMBING - GAS PRESS TEST FNL |
|
Approved |
IVRS - Inspection 0000* |
| 05/21/2002 |
PLUMBING - GAS PRESS TEST FNL |
|
Denied |
IVRS - Inspection 0999*1.) NOBODY HOME 2.) PLEASE SCHEDULE THIS INSPECTION WHEN AN ADULT CAN BE PRESENT TO ASSIST THE INSPECTOR HOURS 7:00 AM - 3:30 PM REINSPECITON 12:30 PM 1.) A FLEX CONNECTOR MAY NOT PASS THRU A PARTITION. HARD PIPE TO OUTSIDE COMBUSTION CHAMBER. 2.) ALL VALVES TO BE AGA OR CSA APPROVED. 3.) WHERE PIPING MEETS THEY SHALL BE JOINED WITH A RIGHT LEFT NIPPLE AND COUPLING. A GROUND JOINT UNION MAY BE USED IN AN EXPOSED EXTERIOR LOCATION WHEN PRECEEDED BY A BLDG SHUT OFF VALVE. |