Permit: T02PL01000

Parcel: 134110430


Addresses:

7918 E 19TH PL

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESS TEST FNL

Date Description Inspector Results Comments
05/22/2002 PLUMBING - GAS PRESS TEST FNL Approved IVRS - Inspection 0000*
05/21/2002 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection 0999*1.) NOBODY HOME 2.) PLEASE SCHEDULE THIS INSPECTION WHEN AN ADULT CAN BE PRESENT TO ASSIST THE INSPECTOR HOURS 7:00 AM - 3:30 PM REINSPECITON 12:30 PM 1.) A FLEX CONNECTOR MAY NOT PASS THRU A PARTITION. HARD PIPE TO OUTSIDE COMBUSTION CHAMBER. 2.) ALL VALVES TO BE AGA OR CSA APPROVED. 3.) WHERE PIPING MEETS THEY SHALL BE JOINED WITH A RIGHT LEFT NIPPLE AND COUPLING. A GROUND JOINT UNION MAY BE USED IN AN EXPOSED EXTERIOR LOCATION WHEN PRECEEDED BY A BLDG SHUT OFF VALVE.