Permit: T02PL00984

Parcel: 13631024B


Addresses:

4880 S HOUGHTON RD

Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Date Description Inspector Results Comments
01/24/2003 PLUMBING - SEWER HCS CONNECT Approved
12/11/2002 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*OK MANHOLE BASES #6,#5,#4,#7.
12/09/2002 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*OK PRESSURE TEST ONLY @ EAST 104 LF FROM M.H. #5 TO CLEAR OUT #2. OK MANHOLE BASE #1 #2 #3.
12/06/2002 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*
1.) AIR PRESSURE TEST FROM M.H. #2 SOUTH TO C.O. #4 IS OK
2.) AIR PRESSURE TEST FROM M.H. #7 EAST TO C.O. #3 IS OK
3.) OK TO BACKFILL TRENCH.
11/24/2002 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*