Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/28/2002 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*1.) AS NOTED ON T02CM02219 PLUMBING SHOULD HAVE BEEN INCLUDED AND NEEDS TO BE INSPECTED 2.) ALL GAS CORRECTIONS MADE OK 3.) OK FOR GAS 4.) UCC LEFT AT METER. |
| 05/16/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) PVC NOT APPROVED MAT'L FOR T & P DRAIN. DRAIN MUST HAVE PITCH DOWN HILL TO TERMINATION 2.) GAS FLEX FOR FURNACE MAY NOT PASS THROUGH WALL OR PARTITION. 3.) NO TRAP ON WASHER DRAIN. 4.) SECURE PERMIT FOR NEW WATER LINE PVC NOT APPROVED ABOVE GRADE. HOSE BIBB REQUIRE VACUUM BREAKER 5.) GAS LINE REQUIRES FLASHING THROUGH ROOF 6.) NO STRAPPING ON BLOCKS ON ROOF. 7.) DISHWASHER DRAIN NOT APPROVED PERMITS FOR NEW FIXTURES. |
| 05/14/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999* |