Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/28/2002 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 05/14/2002 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) MUST RUN P & T DRAIN TO DAYLIGHT OR APPROVED RECEPTOR YOUR OPTION IS TO APPEAL THIS ISSUE TO THE CODES ADMINISTRATOR WITH PROPER FORMS. 2.) CAN NOT HAVE FLEX LINE IN P & T DRAIN THIS DRAIN MUST BE FULL SIZE ALL THE WAY TO DAYLIGHT. 3.) MUST PROVIDE AIR PRESSURE TEST @ TIME OF INSPECTION 10LBS MIN 4.) MUST SCREW DOWN FLU VENT @ COLLAR AND ALL JOINTS (3) SCREWS PER JOINT. 5.) MUST SECURE ALL GAS DROPS WITH APPROVED TWO HOLE STRAPS. |