Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/16/2002 |
PLUMBING - FINAL |
|
Approved |
1.) GAS PRESSURE TEST IS OK 2.) GAS SHUT OFF VALVES ARE OK 3.) WATER HTR FLU VENT, P & T VALVE & DRAIN IS OK. |
| 05/14/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) WATER HTR REQUIRES A ENCLOSURE TO PROTECT IT FROM THE ELEMENTS 2.) MUST REMOVE ASBESTOS FLU VENT AND REPLACE WITH DBL WALL FLU VENT THRU ROOF W/CAP MUST EXTEND P & T DRAIN AND TERMINATE 6 A.F.F. |