Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/17/2002 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*1.) GAS PRESSURE TEST IS OK 2.) GAS SHUT OFF VALVES ARE OK 3.) WATER HTR FLU VENT CAP P & T VALVE & DRAIN IS OK 4.) FURANCE FLU VENT IS OK 5.) OK TO BACKFILL TRENCH. |
| 05/09/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) MUST SCREW DOWN WATER HTR FLU VENT WITH (3) SHEET METAL SCREWS PER JOINT @ COLLAR & FLU VENT. 2.) CAN NOT HAVE FLEX LINE IN P & T DRAIN. 3.) IT APPEAR THAT GAS LINE BY METER & FENCE DOES NOT MEET THE MIN DEPTH OF 18" |