Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T02PL00871
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2002 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* | |
| 04/29/2002 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) SEE 608.5 94UPC T & P RELIEF TERMINATION 2.) SEE 510.6 94UPC WATER HEATER SUPPORT 3.) SEE 517.3 VENT TERMINATION 4.) WATER HEATER NOT LEVEL CLEARANCES NOT MAINTAINED 5.) ENCLOSURE NOT SECURE 6.) NO TOP ON ENCLOSURE 7.) INSTALL VACUUM BREAKER ON HOSE BIBB. | |
| 04/25/2002 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) CHANGE GALVANIZED 3/4 NIPPLES TO BRASS 2) INSTALL GALVANIZED 3/4 90 ON END OF TPRV DISCHARGE LINE 3) PROVIDE 1" MINIMUM CLEARANCE AROUND VENT PIPING |