Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 04/24/2002 |
PLUMBING - GAS PRESSURE TEST |
|
Approved |
IVRS - Inspection 0000* |
| 04/23/2002 |
PLUMBING - GAS PRESSURE TEST |
|
Denied |
IVRS - Inspection 0999*1.) WATER HTR #1 REQUIRES A P & T VALVE AND DRAIN TO DAYLIGHT. 2.) CAN NOT HAVE FLEX LINE IN P & T DRAIN 3.) IF YOU CHOOSE TO DISCHARGE P & T DRAIN INTO RECEPTOR THEN THIS LINE MUST HAVE A 1" AIR GAP AND BOTH P & T DRAINS MUST GO INTO 1 1/4" LINE 4.) MUST SCREW DOWN FLY VENT WITH (3) SHEET METAL SCREWS PER JOINT. 5.) MUST BLOCK & STRAP GAS LINE ON ROOF EVERY 6' 6.) OK TO BACKFILL TRENCH. |