Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
04/24/2002 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection 0000*
04/23/2002 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*1.) WATER HTR #1 REQUIRES A P & T VALVE AND DRAIN TO DAYLIGHT. 2.) CAN NOT HAVE FLEX LINE IN P & T DRAIN 3.) IF YOU CHOOSE TO DISCHARGE P & T DRAIN INTO RECEPTOR THEN THIS LINE MUST HAVE A 1" AIR GAP AND BOTH P & T DRAINS MUST GO INTO 1 1/4" LINE 4.) MUST SCREW DOWN FLY VENT WITH (3) SHEET METAL SCREWS PER JOINT. 5.) MUST BLOCK & STRAP GAS LINE ON ROOF EVERY 6' 6.) OK TO BACKFILL TRENCH.