Permit: T02PL00728

Parcel: 107081220


Addresses:

710 W TIPTON DR

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
04/21/2002 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*
04/18/2002 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*PLEASE HAVE YOUR PLUMBER READ OVER SEC 313.8 94 UPC PLEASE PROVIDE APPROVED FLASHING RETEST & CALL AGAIN. PROBLEM WITH PERMIT CALL STEVE LONG 791-5550 147.
04/16/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) NEED SEPERATE PERMIT FOR GAS PIPING AND PRESSURE TEST
04/11/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) NEED 1" CLEARANCE AROUND VENT PIPING THROUGH ROOF 2) NEED 3 SCREWS IN EA JOINT ON VENT PIPING FROM VENT CONNECTOR UP 3) CANNOT USE FLEX LINE ON T.P.R.V. DISCHARGE LINE 4) NEED PRESSURE TEST ON TOTAL GAS SYTEM 5) SUPPORT GAS PIPING TO WALL FOR DRYER AND WATER HEATER