Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/03/2002 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*1.) OVERHEAD WATER DISTRIBUTION IS OK 2.) HYDROSTATIC TEST ON SYSTEM IS OK 3.) OK FOR DRYWALL. |
| 04/02/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) MUST PROVIDE HYDROSTATIC TEST ON WATER DISTRIBUTION @ TIME OF INSPECTION. 2.) MUST REMOVE AND REPLACE ALL COPPER WATER LINES THAT ARE KINKED SEE SECTION: 310.1 94 UPC 3.) MUST PROTECT COPPER LINES THAT ARE TOUCHING BLOCK WALL 4.) WHAT IS SERVIING COOLER LINE? IT APPEARS THAT 1/2" COPPER IS INSERTED INTO P.B. MATERIAL. THIS IS UNACCEPTABLE 5.) CHECK ENTIRE SYSTEM FOR LOOSE LINES 6.) DO NOT TAPE HOT & COLD TOGETHER 10MIL TAPE IS NOT A APPROVED METHOD OF STRAPING. 7.) VERY POOR WORKMANSHIP ON MUST SOULDERED JOINTS. |
| 04/01/2002 |
PLUMBING - FINAL |
|
Not ready for Inspection |
NOT READY FOR INSPECTION. |