Permit: T02PL00714

Parcel: 110043680

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/03/2002 PLUMBING - FINAL Approved IVRS - Inspection 0000*1.) OVERHEAD WATER DISTRIBUTION IS OK 2.) HYDROSTATIC TEST ON SYSTEM IS OK 3.) OK FOR DRYWALL.
04/02/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) MUST PROVIDE HYDROSTATIC TEST ON WATER DISTRIBUTION @ TIME OF INSPECTION. 2.) MUST REMOVE AND REPLACE ALL COPPER WATER LINES THAT ARE KINKED SEE SECTION: 310.1 94 UPC 3.) MUST PROTECT COPPER LINES THAT ARE TOUCHING BLOCK WALL 4.) WHAT IS SERVIING COOLER LINE? IT APPEARS THAT 1/2" COPPER IS INSERTED INTO P.B. MATERIAL. THIS IS UNACCEPTABLE 5.) CHECK ENTIRE SYSTEM FOR LOOSE LINES 6.) DO NOT TAPE HOT & COLD TOGETHER 10MIL TAPE IS NOT A APPROVED METHOD OF STRAPING. 7.) VERY POOR WORKMANSHIP ON MUST SOULDERED JOINTS.
04/01/2002 PLUMBING - FINAL Not ready for Inspection NOT READY FOR INSPECTION.