Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 04/02/2002 |
PLUMBING - GAS PRESSURE TEST |
|
Approved |
IVRS - Inspection 0000* 1.) GAS PRESSURE TEST IS OK 2.) GAS SHUT OFF VALVES OK 3.) WATER HTR FLU VENT, P & T DRAIN & VALVE IS OK 4.) FURNACE IS OK. |
| 04/01/2002 |
PLUMBING - GAS PRESSURE TEST |
|
Denied |
IVRS - Inspection 0999*1.) CAN NOT HAVE ANY FLEX CONNECTOR PENETRATE CABINET WALL. MUST HARD PIPE GAS LINE THROUGH CABINET WALL THEN CONNECT SHUT OFF VALVE & FLEX. 2.) MUST COMPLETE 1/2" GAS LINE @ WATER HTR AND RE TEST SYSTEM TO 10LBS MIN. |