Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/03/2002 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 04/03/2002 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*1.) PRESSURE TEST OK 2.) OK TO RECONNECT MIT 3.) OK FOR GAS 4.)UCC LEFT AT METER. |
| 04/01/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 03/29/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) PIPING FROM METER TO MH REQ'D 10# MINIMUM TEST PIPING FOR MOBILEHOME ONLY REQUIRES 3# TEST. 2.) UNION ON WRONG SIDE OF VALVE NOT NECESSARY. REMOVE UNION. FLEX CONNECTOR BECOMES UNION 3.) PRESSURE TEST FOR MOBILE HOME OK NEED TO SEE 10# TEST ON UNDERGROUND PIPING. |