Permit: T02PL00696

Parcel: 140100060

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - FINAL

Permit Number - T02PL00696

Inspection Description - PLUMBING - FINAL

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
04/03/2002 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*
04/03/2002 PLUMBING - FINAL Approved IVRS - Inspection 0000*1.) PRESSURE TEST OK 2.) OK TO RECONNECT MIT 3.) OK FOR GAS 4.)UCC LEFT AT METER.
04/01/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*
03/29/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) PIPING FROM METER TO MH REQ'D 10# MINIMUM TEST PIPING FOR MOBILEHOME ONLY REQUIRES 3# TEST. 2.) UNION ON WRONG SIDE OF VALVE NOT NECESSARY. REMOVE UNION. FLEX CONNECTOR BECOMES UNION 3.) PRESSURE TEST FOR MOBILE HOME OK NEED TO SEE 10# TEST ON UNDERGROUND PIPING.