Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T02PL00687
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/01/2002 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection 0000* | |
| 03/28/2002 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999*ENTER BACKYARD THRU EAST SIDE GATE. METER IN BACK. 1.) REMOVE UNION FROM THE GAS LINEON THE ROOF. USE REVERSE THREAD COUPLINGS & NIPPLES. YOU CAN HAVE A UNION AT THE APPLIANCE IMMEDIATELY PRECEDED BY A SHUT OFF VALVE MUST BE WITHIN 3' OF HTE APPLIANCE. 3.) WATER HEATER ON SIDE OF HOUSE NEEDS A T & P DRAIN LINE. 4.) SYSTEM NOT HOLDING PRESSURE. | |
| 03/26/2002 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999* |