Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T02PL00679
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/22/2002 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*1.) GAS PRESSURE TEST IS OK 2.) GAS SHUT OFF VALVES ARE OK 3.) NOTE: GAS METER IS TO BE RELOCATED BY S.W. GAS GAS, METER IS STILL ENERGIZED. | |
05/20/2002 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection 0000*1.) OK TO COVER GAS LINE TRENCH. 2.) CAN NOT HAVE A UNION IN GAS LINE. WHERE A UNION IS NEEDED YOU MUST USE A RIGHT & LEFT HAND NIPPLE. 3.) REMOVE THREAD PROTECTOR IN GAS LINE & REPLACE WITH APPROVED COUPLING. 4.) RE TEST SYSTEM. | |
05/17/2002 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) MUST USE A APPROVED ROOF FLASHINGS WHERE GAS LINE PENETRATES THE ROOF. 2.) MUST STRAP DOWN GAS LINE O ROOF EVERY 6'-0" WITH GALX. TWO HOLE STRAPS. 3.) RETEST THE SYSTEM 10LBS MIN. |