Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/24/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) VENT PIPING IS CLOSED AT BOTTOM AT VENT CONNECTOR 2) CHECK HORIZONTAL PORTION OF THE T.P.R.V. DISCHARGE LINE, MUST HAVE 1/4" PER FT. DOWNWARD SLOPE 3) VENT PIPING IS INSTALLED UPSIDE DOWN |