Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/21/2002 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000* 1.) 30# TEST GUAGE IN ONE POUND INCREMENTS OK 15# TEST OK 2.) GAS REPAIR OK CONTRACTOR PROVIDED LISTING FOR UPON OR 361661660700 COMPRESSION COUPLING AGA CSA ASTM UPC LISTED. 3.) WATER HEATER ENCLOSURE OK 4.) GAS DROP AT RANGE SECURED. |
| 03/18/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) MUST USE REQUIRED TEST GAUGES FOR PRESSURE TEST. SEE SECTION 712.4.1 94 UPC. 2.) MUST PROVIDE WATER HTR ENCLOSURES FOR BOTH WATER HTRS 3.) MUST REMOVE FLEX LINE IN P & T DRAIN. 4.) PLEASE PROVIDE A LISTINGS ON REPAIR COUPLING FOR UNDERGROUND GAS LINE 5.) MUST SECURE GAS DROP FOR RANGE. |