Permit: T02PL00591

Parcel: 111084090

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
03/27/2002 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection 0000*
03/18/2002 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*1.) MUST USE APPROVED COUPLING IN UNDER GROUND GAS LINE. THREAD PROTECTOR IS NOT A APPROVED COUPLING. 2.) MUST APPLY APPROVED TAPE PRIMER ON ALL APPROVED TAPE PRIMER ON ALL JOINTS UNDERGROUND THEN APPLY 10MIL TAPE 3.) CAN NOT HAVE FLEX LINE IN P & T DRAIN 4.) MUST HAVE 1" CLEARANCE AROUND DBL WALL FLU VENT @ CEILING. 5.) MUST SCREW DOWN DBL WALL FLU VENT WITH (3) SHEET METAL SCREW @ VENT CONNECTOR. 6.) MUST USE TEST GAUGE THAT HAS INCREMENTS OF 1/10 SEE SECTION 712.4.1 94 UPC.