Permit: T02PL00580

Parcel: 133146280

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/20/2002 PLUMBING - FINAL Approved IVRS - Inspection 0000*
03/11/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999* 1.) MUST REPLACE PRESSURE RELIFE VALVE @ BOILER. 2.) MUST APPLY APPROVED TAPE PRIMER TO ALL JOINT UNDERGROUND THEN APPLY 10 MIL TAPE. 3.) UNDERGROUND GAS LINE MUST HAVE A MIN. OF 12" OF COVER CHECK YOUR TRENCH DEPTH. 4.) GAS PRESSURE TEST IS OK 5.) MUST SCREW DOWN FLU VENTS WITH (3) SHEET METAL SCREWS PER JOINTS AND APPLIANCE CONNECTOR.