Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/07/2002 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000* 1.)GAS PRESSURE TEST IS OK 2.) GAS SHUT OFF VALVE OK 3.) NOTE: THIS INSPECTION IS FOR POWER GENERATOR ONLY 4.) OK TO BACKFILL TRENCH. |
| 03/04/2002 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*NOT READY FOR INSPECTION |
| 03/01/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999* 1.) PROVIDE LISTING ON BTU RATEING ON NATURAL GAS GENERATOR. 2.) PIPE GAS LINE DOES NOT MEET MIN COVER OF 18" WHERE GAS LINE CONNECTS TO IRON RISER. |