Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 03/05/2002 |
PLUMBING - GAS PRESSURE TEST |
|
Approved |
1.) GAS PRESSURE TEST IS OK 2.) GAS SHUT OFF VALVES OK 3.) WATER HTR FLU VENT, P & T DRAIN & VALVE IS OK 4.) GAS PACK ON ROOF IS OK. |
| 02/27/2002 |
PLUMBING - GAS PRESSURE TEST |
|
Denied |
IVRS - Inspection 0999*1.) MUST PROVIDE AIR PRESSURE TEST MIN 10 LBS PRIOR TO INSPECTION 2.) MUST BLOCK AND STRAP DOWN GAS LINE EVERY 6'-0" ON ROOF. 3.) MUST HAVE AGA APPROVED GAS SHUT OFF VALVE @ AC UNIT ON ROOF.4.) GAS SHUT OFF VALVE FOR AC UNIT MUST BE WITHIN 3'-0" OF REGULATOR. 5.) REMOVE UNION IN LINE AND REPLACE WITH RIGHT & LEFT HAND NIPPLE OK NEW PIPE. |