Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T02PL00434

Parcel: 120090670

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
03/01/2002 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection 0000*
02/27/2002 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*
02/25/2002 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*1.) ALL VALVES MUST BE AGA OR CSA APPROVED 2.) WHERE PIPING MEETS, THE CONNECTION SHALL BE MADE WITH A RIGHT -LEFT NIPPLE AND COUPLING. 3.) ALL GAS PIPING LESS THAN 6" ABOVE GRADE MUST BE SCOTCH COAT PIPE AND ALL FITTINGS WRAPPED W/10 MIL TAPE 4.) I WOULD LIKE TO SEE AN ISOMETRIC DRAWING SHOWING DEVELOPED LENGTH AND TOTAL BTU'S.
02/20/2002 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*1.) METER PINNED 2.) NO PRESSURE TEST. NEED TO HOLD 10# TEST 3.) ALL VALVES TO BE AGA OR CSA APPROVED. 4.) EXTEND T & P RELIEF DRAIN TO - 6" AFF.