Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 02/21/2002 |
PLUMBING - GAS PRESSURE TEST |
|
Approved |
IVRS - Inspection 0000* |
| 02/20/2002 |
PLUMBING - GAS PRESSURE TEST |
|
Denied |
IVRS - Inspection 0999*1.)MUST EXTEND 1" GAS LINE ALL THE WAY TO METER. 2.)MUST EXTEND HARD PIPE OUT OF APPLIANCE HOUSING @ FURNACE 3.) MUST REPLACE ASBESTOS FLU VENT FOR WATER HTR AND INSTALL DBL WALL FLU VENT & CAP. 4.) MUST SCREW DOWN FLU VENT TO VENT CONNECTOR WITH (3) SHEET METAL SCREWS PER JOINT. 5.) MUST VERIFY OR REPLACE P & T VALVE @ WATER HTR THAT TEMP. PROBE EXTENDS INTO TANK. 6.) P & T DRAIN MUST GO TO DAYLIGHT AND PROVIDE UNION IN LINE 7.) RE TEST SYSTEM. |