Permit: T02PL00393

Parcel: 13343341B


Addresses:

10210 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - PROGRESS

Permit Number - T02PL00393

Inspection Description - PLUMBING - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
06/04/2002 PLUMBING - PROGRESS Approved IVRS - Inspection 0000*1.) MANDREL HAS BEEN PULLED ON ENTIRE 8" SITE SEWER.
05/23/2002 PLUMBING - PROGRESS Partial Approval 1.) AIR PRESSURE TEST FOR 6" SEWER MAIN FROM M.H. #7 EAST TO C.O. #34 IS OK. 2.) AIR PRESSURE TEST FOR 6" SEWER MAIN FROM M.H. #9 WEST TO C.O. #54 IS OK. 3.) AIR PRESSURE TEST FOR 6" SEWER MAIN FROM M.H. #9. SOUTH TO C.O. 50 IS OK.
05/22/2002 PLUMBING - PROGRESS Partial Approval IVRS - Inspection 0000*1.) AIR PRESSURE TEST FOR 6" SEWER MAIN FROM M.H. #9 TO C.O. #46 IS OK 2.) AIR PRESSURE TEST FOR 6" SEWER MAIN FROM M.H. #8 SOUTH TO C.O. 40 AND WEST TO C.O. 37 IS OK.
05/21/2002 PLUMBING - PROGRESS Partial Approval IVRS - Inspection 0000* 1.) 6" MAIN FROM M.H. #4 NORTH TO C.O. 18 AIR PRESSURE TEST IS OK 2.) 6" MAIN FROM M.H. #4 SOUTH TO CO. 20 AND WEST BRANCH TO C.O. 23 AIR PRESSURE TEST IS OK. 3.) AIR PRESSURE TEST FOR 6" MAIN FROM M.H. #5 TO C.O. 27' IS OK 2.) AIR PRESSURE TEST FOR 6" MAIN FROM M.H. #6 EAST TO C.O. 32 IS OK.
05/20/2002 PLUMBING - PROGRESS Partial Approval IVRS - Inspection 0000*1.) AIR PRESSURE TEST FROM M.H. #10 EAST TO C.O. #15 IS OK 2.) AIR PRESSURE TEST FROM M.H. #11 EAST TO C.O. #58 IS OK 3.) AIR PRESSURE TEST FROM M.H. #11 SOUTH TO C.O. #63 IS OK. 4.) AIR PRESSURE TEST FROM M.H. #11 SOUTH TO C.O. #67 IS OK.
05/17/2002 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection 0000*N.R. READY FOR INSPECTION
05/16/2002 PLUMBING - PROGRESS Partial Approval 1.) 8" SITE SEWER AIR PRESSURE TEST IS OK FOR M.H. #10 SOUTH TO M.H. #11 IS OK 2.) AIR PRESSURE TEST FROM M.H. #10 WEST TO C.O. #8 AND SOUTH TO C.O. 10 IS OK 3.) 8" X 4" HCS FOR LOTS 25 & 26.
05/14/2002 PLUMBING - PROGRESS Partial Approval IVRS - Inspection 0000*1.) AIR TEST FOR 8" SEWER MAIN FROM M.H. 1 TO NORTH EXSISTING M.H. @ P.L. IS OK 2.) AIR TEST FROM M.H. #1 EAST TO C.O. #3 IS OK. 3.) AIR TEST FROM MH #1 SOUTH TO M.H. #2 IS OK 4.) 4" HCS FOR PADS #61 & 62 IS OK 5.) SITE SEWER FROM C.O. #50 EAST TO C.O. 48 NORHT TO M.H. #9. 6.) SITE SEWER FROM C.O. #45 EAST TO C.O. #44 TO C.O. 46 WEST TO C.O. 44 AND C.O. 44 NORTH TO C.O. #41 AND C.O. 41 WEST TO M.H. #9 IS OK. 7.) M.H. #9 WEST TO C.O. #53 AND FROM C.O. #53 SOUTH TO C.O. #54 WEST TO C.O. #55.
05/13/2002 PLUMBING - PROGRESS Partial Approval IVRS - Inspection 0000*1.) AIR TEST ON 8" SEWER MAIN FROM M.H. #3 TO M.H. #4 IS OK 2.) AIR TEST ON 8" SEWER MAIN FROM M.H. #2 TO M.H. 3 AND SR #8,9,10,& 11 IS OK 3.) AIR TEST ON 8" SEWER MAIN FROM M.H. #3 TO M.H. #10 IS OK.
05/09/2002 PLUMBING - PROGRESS Partial Approval 6" SITE SEWER FROM C.O. #29 EAST TO SOUTH C.O. 34 IS OK TO BACKFILL. 2.) NOTE: SITE SEWER REQUIRES A MIN OF 12" OF COVER FROM SUB GRADE.
05/08/2002 PLUMBING - PROGRESS Partial Approval IVRS - Inspection 0000*1.) 6" SITE SEWER FROM M.H. #5 TO UPSTREAM C.O. #27 AND M.H. #6 EAST TO C.O. #29 IS OK FOR BACKFILL. 2.) AIR PRESSURE TEST FOR 8" SEWER MAIN FROM MH #4 WEST TO M.H. #3 NOT HOLDING. 3.) AIR PRESSURE TEST FROM M.H. #3 SOUTH TO M.H. #10 DID NOT TEST.
05/07/2002 PLUMBING - PROGRESS Partial Approval 1.) AIR PRESSURE TEST ON 8" SITE SEWER MAIN IS OK FROM M.H. #7 T0 6,5, AND 4. 2.) PULLED MANDRELL THRU SITE SEWER FROM M.H. 8,7,6,5,&4. ONLY.
05/06/2002 PLUMBING - PROGRESS Partial Approval IVRS - Inspection 0000*1.) AIR PRESSURE TEST IS OK FOR SITE SEWER FROM M.H. #9 NORHT TO M.H. #8 AND WEST TO M.H. #7. 2.) PULLED OK THRU SITE SEWER FROM M.H. #9 NORTH TO M.H. #8. 3.) M.H. #4 SITE SEWER 6" SOUTH TO END C.O. IS OK.
05/02/2002 PLUMBING - PROGRESS Partial Approval IVRS - Inspection 0000*1.) 6" SITE SEWER MAIN FROM M.H. #1 TO EAST C.O. #3 IS OK 2.) 6" SITE SEWER FROM M.H. #10 EAST TO C.O. #15 IS OK 3.) 8" SITE SEWER FROM MH. #1 TO M.H. #9 OK MAIN ONLY NO LATTERALS. 4.) 6" SITE SEWER FROM M.H. #4 TO C.O. 16,17,18, ONLY IS 5.) 6" SITE SEWER FROM M.H. #10 EAST TO C.O. #15 ONLY IS OK.
05/01/2002 PLUMBING - PROGRESS Partial Approval IVRS - Inspection 0000*1.) 6" SITE SEWER FROM C .O. #56 EAST TO C.O. #58 ONLY. 2.) OK TO BACKFILL TRENCH.
04/30/2002 PLUMBING - PROGRESS Partial Approval IVRS - Inspection 0000*1.) SITE SEWER 6" MAIN FROM 5.65 C.O. TO 5-68 AND 569 THRU 573 IS OK 2.) SITE SEWER 6" MAIN FROM M.H. #11 THRU C.O. #56 IS OK 3.) OK TO BACKFILL TRENCH.
04/25/2002 PLUMBING - PROGRESS Partial Approval 1.) SITE SEWER OK FROM S-9,10,11,12,13,& 14 AND S-64 NORTH TO MANHOLE #11. 2.) OK TO BACKFILL TRENCH 3.) EXPOSED SECTION OF MAIN IS OK TO BACKFILL.
04/05/2002 PLUMBING - PROGRESS Partial Approval IVRS - Inspection 0000*1.) MECHANICAL FLEXIBLE JOINTS ON INLET & OUT LET OF 8" MAIN IS OK 2.) WILL SEE AIR TEST @ LATER TIME.
03/29/2002 PLUMBING - PROGRESS Partial Approval 1.) BASES HAVE BEEN SET FOR M.H. 3,8,9,10,11 IS OK TO STACK & BACKFILL TRENCH.
03/28/2002 PLUMBING - PROGRESS Denied IVRS - Inspection 0999*1.) CONTRACTOR HAS COVERED APPROX. 600' OF PRIVATE SEWER PRIOR TO INSPECTION SEE SECTION: 103.5.1.3, 103.5.1.4. 94 UPC 2.) SITE SEWER FROM M.H. #10 SOUTH TO M.H. #11 ISOK TO BACKFILL 3.) NOTE: WILL REQUIRE A SURYEYOR TO VERIFY & CERTIFY GRADE @ TIME OF FINAL EVERY 50' INTERVALS.
03/27/2002 PLUMBING - PROGRESS Partial Approval IVRS - Inspection 0000*1.) BASES HAVE BEEN SET FOR M.H. 1,2,4,5,6,7 OK TO STACK & BACKFILL. 2.) 8" SITE SEWER FROM M.H. #3 TO M.H. #10 OK TO BACKFILL TRENCH. 3.) CONTRACTOR WILL PROVIDE AIR TEST OF 5LBS MIN @ LATER TIME. 4.) 6" SEWER MAIN FROM M.H. #7 EAST TO C.O. #34 IS OK FOR BACKFILL.