Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/06/2002 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.) MUST PROVIDE A AIR PRESSURE TEST 10LBS MIN. 2.) MUST REMOVE P & T VALVE AND REPLACE WITH NEW WORKING VALVE 3.) MUST PROVIDE AGA OR CSA GAS SHUT OFF VALVE FOR WATER HTR. 4.) MUST SCREW DOWN FLU VENT TO APPLIANCE COLLAR AND ALL JOINTS WITH (3) SHEET METAL SCREWS |
| 02/05/2002 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) NO ONE HOME! SORRY WE MISSED YOU PLEASE CALL 791-5550 IF YOU NEED TO MAKE A APPOINTMENT. |