Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/22/2002 |
PLUMBING - INTERMEDIATE |
|
Approved |
|
| 03/08/2002 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) GAS PRESSURE TEST IS OK. 2.) NOTE; THIS INSPECTION IS FOR UNDERGROUND GAS LINE FROM METER TO BLDG.ONLY. 3.) MUST SEE FINAL CONNECTION TO ALL GAS APPLIANCES @ DWELLING THEN I WILL RELEASE THE GAS CLREANCE CARD 4. OK TO BACKFILL TRENCH. |
| 03/07/2002 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) MUST USE PROPER TEST GAUGE FOR GAS LINE REQUIRNG 10LBS OR LESS SEE SECTION 712.4.1. 94 UPC 2.) I APPEAR THAT GAS LINE BY THE METER LOCATION DOES NOT MEET THE MIN. DEPTH. |