Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/07/2002 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*1.) ALL CORRECTIONS MADE OK 2.) GAS OK UCC LEFT AT METER 3.) WATER HEATER OK. |
| 02/05/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) GAS PIPIN APPROVED 1/30/02 BY R MYERS 2.) WATER HEATER T & P RELIEF DRAIN OK CLEARANCE OK SUPPLY FLEXES OK VENTSYSTEM SECURE VENT CONNECTOR TO COLLAR WITH 3 SCREWS DO NOT TAPE DOUBLE WALL 1" CLEARANCE REQUIRED FROM COMBUSTIBLES WITH WALL VENT AN OATEY, METAL AND NEOPRENE, ROOF JACK IS NOT APPROVED. FOR GAS VENTING USE GALVANIZED FLASHING OR OTHER APPROVED FLASHING FOR GAS VENTING USE GALVANIZED FLASHING OR OTHER APPROVED FLASHING. |
| 01/30/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) SECURING A PERMIT FOR THE WATER HEATER IS NOT AN OPTION: IT IS MANDATORY. 2.) I CANNOT RELEASE GAS FOR AN UNAPPROVED APPLIANCE. HAVE WATER HEATER INSPECTED, AS YOU WOULD ALL NEW WATER HEATER INSTALLATIONS, AND THEN GAS CAN BE RELEASED 3.) PRESSURE TEST OK 4.) PIPING OK 5.) VALVES AND FLEXES OK. |