Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/08/2002 |
PLUMBING - FINAL |
|
Approved |
1.) GAS PRESSURE TEST IS OK 2.) GAS SHUT OFF VALVES IS OK 3.) WATER HTR FLU VENT, P&T DRAIN & VALVE IS OK 4.) OK TO BACKFILL TRENCH. |
| 01/28/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) GAS PRESSURE TEST WAS DONW TO 2LB ONLY. MUST PROVIDE 10LB TEST MIN. 2.) MUST USE TAPE PRIMER AND APPLY 10 MIL TAPE TO ALL JOINTS AND SMALL NIPPLES & PIPE UNDERGROUND. 3.) MUST HAVE 1" CLEARANCE AROUND DBL WALL FLU VENT FOR WATER HTR & FURNACE. 4.) MUST PROVIDE UNION IN P & T DRAIN 12" MAX FROM VALVE. 5.) STRAP DOWN 1/2" COPPER IN WALL & PROVIDE SAFTEY PLATE. |