Permit: T02PL00222

Parcel: 11806087J

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T02PL00222

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/03/2002 PLUMBING - FINAL Approved IVRS - Inspection 0000*
03/27/2002 PLUMBING - FINAL Partial Approval 1.) REVIEWED APPROVED PLAN INSTALLED PER PLAN 2.) OK TO SHADE GAS LINE WILL NEED TO SEE SHADED PIPE AS NATURAL SOILS ARE WAY TOO ROCKY.
03/22/2002 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*1.) PROVIDE CITY APPROVED PLAN NOT READY FOR INSPECTION.
03/21/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) ALL COMMERCIAL JOBS REQUIRE A PLAN. I'M CONCERNED ABOUT THREE LOTS ON ONE METER ESPECIALLY WITH THE RISE IN ELEVATION TO LOT "B" WATER GAS REQUIRES AN ISOMETRIC WITH TOTAL DEVELOPED LENGTH AND BTU CONSUMPTION. 2.) PIPING 6" ABOVE GRADE AND BELOW TO BE SCOTCHCOAT ALL MARRED PIPING TO BE FIELD WRAPPED. 3.) ALL PVC WATER PIPE REQUIRES A MINIMUM OF TWELVE INCHES OF COVER. 4.) EXPOSE ALL FITTINGS.