Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 06/05/2002 |
PLUMBING - SEWER HCS CONNECT |
|
Approved |
IVRS - Inspection 0000*1.) AIR PRESSURE TEST ON ENTIRE SYSTEM IS OK. |
| 04/03/2002 |
PLUMBING - SEWER HCS CONNECT |
|
Partial Approval |
IVRS - Inspection 0000*1.) MANHOLE INLET AND OUTLET SIDE REQUIRES A FLEXIBLE COMPRESSION JOINT ON ALL MANHOLES SEE SECTION 719.6 94 UPC 2.) SITE SEWER FROM MANHOLE #4 TO C.O. #3 HCS FOR LOTS 12,13,14,15,OK 3.) HCS FOR LOTS 1,2, & 6 OK 4.) OK TO BACKFILL TRENCH. |
| 03/29/2002 |
PLUMBING - SEWER HCS CONNECT |
|
Partial Approval |
1.) 8" SITE SEWER FROM M.H. #2 NORTH TO C.O. #1 AND M.H. #2. EAST TO C.O. #2 HCS FOR 3,4,5,6,8,9,10 & 11. ARE OK 2.) OK TO BACKFILL TRENCH. |
| 03/28/2002 |
PLUMBING - SEWER HCS CONNECT |
|
Partial Approval |
IVRS - Inspection 0000*1.) 4" SITE SEWER HCS STUBB OUT FOR 3 LOTS BETWEEN M.H. #3 AND M.H. #4. 2.) OK TO BACKFILL TRENCH.F 3.) AIR TEST WILL BE PROVIDED @ LATER TIME. |
| 03/27/2002 |
PLUMBING - SEWER HCS CONNECT |
|
Partial Approval |
1.) MANHOLE BASES FOR M.H. # 3 & 4. ARE OK 2.) OK TO STACK COLLARS & BACKFILL TRENCH. |
| 03/26/2002 |
PLUMBING - SEWER HCS CONNECT |
|
Partial Approval |
IVRS - Inspection 0000* 1.) 8" SDR 35 SITE SEWER IS OK TO BACKFILL FROM M.H. #3 TO M.H. #4. 2.) AIR TEST WILL BE PROVIDED @ LATER TIME. |
| 03/22/2002 |
PLUMBING - SEWER HCS CONNECT |
|
Partial Approval |
IVRS - Inspection 0000*1.) 8" SDR 35 FROM MANHOLE #2 TO MANHOLE #3 OK AIR TEST AT A LATER DATE. 2.) FROM MANHOLE #2 TO CLEAN OUT #1 40' INCLUDING 4" STUB FOR LOT #7 AND 20' FROM 8" MAIN. 3.) LAST 13' FROM EXISTING MANHOLE TO MANHOLE #2 OK. |
| 03/21/2002 |
PLUMBING - SEWER HCS CONNECT |
|
Partial Approval |
IVRS - Inspection 0000*1.) 8"SDR 35 FROM EXISTING MANHOLE 63' TOWARDS MANHOLE #2 OK MANHOLE TAP OK PIPE OK WILL AIR TEST AT A LATER DATE. 2.) OK TO COVER THIS SECTION. |