Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/11/2002 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*1.) APPROVED BY R MYERS. |
| 01/10/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) I SPOKE AT LENGTH WITH THE PLUMBER, EXPLAINING WHY SCH 40 PVC M/ADPT WERE NOT TO BE USED ON WATER PIPING. HE KNOWS THAT A SCH 80 PVC NIPPLE JOINED WIHT APPROVED SOLVENT CEMENT IS REQUIRED. 2.) I DID NOT GIVE PERMISSION TO COVER THE PIPE, AND HE KNOWS THE LETTERING MUST BE VISIBLE. DEPTH REQUIRED IS TWELVE INCHES MINMUM OF COVER, AND I WILL MEASURE IT. 3.) VACUUM BREAKERS ARE NOT INSTALLED UNTIL THE RESTRAINING SCREW IS BROKEN OFF. |