Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T02PL00032
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/11/2002 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*1.) APPROVED BY R MYERS. | |
01/10/2002 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) I SPOKE AT LENGTH WITH THE PLUMBER, EXPLAINING WHY SCH 40 PVC M/ADPT WERE NOT TO BE USED ON WATER PIPING. HE KNOWS THAT A SCH 80 PVC NIPPLE JOINED WIHT APPROVED SOLVENT CEMENT IS REQUIRED. 2.) I DID NOT GIVE PERMISSION TO COVER THE PIPE, AND HE KNOWS THE LETTERING MUST BE VISIBLE. DEPTH REQUIRED IS TWELVE INCHES MINMUM OF COVER, AND I WILL MEASURE IT. 3.) VACUUM BREAKERS ARE NOT INSTALLED UNTIL THE RESTRAINING SCREW IS BROKEN OFF. |