Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T02OT01697

Parcel: 10603026A


Addresses:

3450 N STONE AV


Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Permit Number - T02OT01697

Inspection Description - SIGN ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
04/15/2003 SIGN ELECTRIC Approved IVRS - Inspection 0000*CKT IN APT 135.
03/27/2003 SIGN ELECTRIC Denied IVRS - Inspection 0935*
1.) PLEASE HAVE YOUR LICENSED ELECTRICAL CONTRACTOR CONTACT ME. THERE ARE FAR TOO MANY VIOLATIONS WITH THIS SIMPLE BRANCH CIRCUIT FOR ME TO LIST.
2.) SEE #4 ABOVE.
3.) SEE #5 ABOVE.
4.) A RE INSPECTION FEE WILL HAVE TO BE PAID @ 201 N. STONE.
03/13/2003 SIGN ELECTRIC Denied IVRS - Inspection 0999*
1.) UNDERGROUND ELECTRIC INSPECTION REQUIRED. UNCOVER ALL CONUIT.
2.) SCHEDULE 80 CONDUIT REQUIRED ABOVE GROUND.
3.) REPAIR BROKEN CONDUIT.
4.) PROVIDE LOAD CALCULATION FOR OUTDOOR LIGHTING CIRCUIT W/SIGN CONNECTED.
5.) PROVIDE ACCESS TO CIRCUIT PANEL.
12/19/2002 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection 0000*