Permit: T02OT01610

Parcel: 138020690


Addresses:

5736 S 12TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/26/2002 ELECTRIC - FINAL Approved
11/21/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*THE SERVICE HAS BEEN ENERGIZED WITHOUT AUTHORIZATION FROM DEVELOPMENT SERVICES. NEUTRAL NOT TERMIDNATED AT SERVICE LABEL PANEL "A" AND PANEL "B" A REINSPECTION FEE IS DUE BEFORE THE NEXT INSPECTOR.
10/30/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) SERVICE TO BE LOWERED SO THAT CENTER OF DISCONNECT HANDLE IS NOT OVER 6FT - 7 " IN HEIGHT. 2.)REVISE PLANS TO SHOW NEW DROP CEILING LIGHTER, CIRCUITS AND REFLECTED CEILING PLAN. HAVE APPROVED PLANS FOR BUILDING AND ELECTRICAL UPON NEXT INSPECTION.
10/11/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*THE ELECTRIC SERVICE EXIST IN A DILAPIDATED, DUE TO OLD AGA, ON BLADES, WEATHERED INSULATION, NON RAINTIGHT EQUIPMENT, IMPROPER WIRING METHODS AT WEATHER HEAD, SERVICE IS TO BE UPGRADED DUE TO ITS DETERIATION CONDITION. 2.) INTERIOR PANEL NEEDS TO BE CLEANED UP EXCESS WIRING 3.) WIRING ABOVE PANEL COVER J-BOX'S. 4.) GENERAL AREA CLOSE OFF OPEN J-BOXES REPAIR OR REMOVE UNWORKING FIXTURES CLEAN UP OF FIXTURES. 5.) RECEPTACLES IN CLOSED OFF AREA TO BE REPAIRED. 6.) ROOF TO HAVE CONDUITS REDONE INSTALLATION TO BE IN A SAFE MANNER REMOVING ELECT HAZARDS. ROOF SAME FOR 5738. WALKED THRU WITH QUALITY ELECT SAME.