Inspection Status: Denied
Inspection History: SIGN SHOP
Permit Number - T02OT01085
Inspection Description - SIGN SHOP
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/15/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NEED PAPERWORK TO IDENTIFY SIGNS TO PLANS & PERMITS 2. A MARKING LABEL IS NEEDED 600.4 3. A SWITCH IS NEEDED 600.6 4. M/C CABLE TO TERMINATE AND SUPPORTED 5. USE APPROVED FITTINGS WITH SEAL TITE 6. PLEASE VERIFY POWER & CIRCUIT PER 600.5 |
|
11/14/2007 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY JOHN |