Permit: T02OT01085

Parcel: 13338005E


Addresses:

10380 E BROADWAY BL


Inspection Status: Denied

Inspection History: SIGN SHOP

Permit Number - T02OT01085

Inspection Description - SIGN SHOP

Inspection Status - Denied

Date Description Inspector Results Comments
11/15/2007 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NEED PAPERWORK TO IDENTIFY SIGNS TO PLANS & PERMITS
2. A MARKING LABEL IS NEEDED 600.4
3. A SWITCH IS NEEDED 600.6
4. M/C CABLE TO TERMINATE AND SUPPORTED
5. USE APPROVED FITTINGS WITH SEAL TITE
6. PLEASE VERIFY POWER & CIRCUIT PER 600.5
11/14/2007 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
CANCELLED BY JOHN