Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
Permit Number - T02OT00980
Inspection Description - SIGN ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/12/2002 | SIGN ELECTRIC | Approved | IVRS - Inspection 0000* | |
08/05/2002 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999*1.) REMOVE ENOUGH OF OUTER COATING ON LIQUID TIGHT CONDUIT @ HIGH VOLTAGE SPLICE SO THAT THERE IS A GOOD METAL TO METAL BOND. 2.) SECURE CONDUIT LENGHTS OVER 3 1/2' LONG @ 4' INTERVALS AND WITHIN 12" OF EACH TERMINATION POINT. USE APPROVED CONDUIT CLAMPS. | |
07/18/2002 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection 0000*INSTRUMENTAL MUSIC NEON PLAN CHANNEL DOUBLE BACK THROUGH WALL. |