| 07/15/2002 |
SIGN ELECTRIC |
|
Approved |
IVRS - Inspection 0000* |
| 07/09/2002 |
SIGN ELECTRIC |
|
Denied |
IVRS - Inspection 0999*1.) FLEXIBLE CORDS NOT ALLOWED ABOVE CEILING. PLUG RECEPTACLE OUTLET FOR PORTABLE OPEN SIGN MUST BE RELOCATED TO BELOW CEILING. NEC 400-8. 2.) 1/2" FLEX CONDUIT CONTAINING PRIMARY WIRING NOT PROPERLY SECURED, NEC 350-18. 3.) JUNCTION OF ARMOURED CABLE WITH 1/2" CONDUIT NOT TERMINATED IN PROPER JUNCTION BOX NEC 300-15. |
| 06/18/2002 |
SIGN ELECTRIC |
|
Not ready for Inspection |
IVRS - Inspection 0000*WE BOY GOLD NEON ON RACEWAY. |