Permit: T02OT00820

Parcel: 12213055E

Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Date Description Inspector Results Comments
07/15/2002 SIGN ELECTRIC Approved IVRS - Inspection 0000*
07/09/2002 SIGN ELECTRIC Denied IVRS - Inspection 0999*1.) FLEXIBLE CORDS NOT ALLOWED ABOVE CEILING. PLUG RECEPTACLE OUTLET FOR PORTABLE OPEN SIGN MUST BE RELOCATED TO BELOW CEILING. NEC 400-8. 2.) 1/2" FLEX CONDUIT CONTAINING PRIMARY WIRING NOT PROPERLY SECURED, NEC 350-18. 3.) JUNCTION OF ARMOURED CABLE WITH 1/2" CONDUIT NOT TERMINATED IN PROPER JUNCTION BOX NEC 300-15.
06/18/2002 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection 0000*WE BOY GOLD NEON ON RACEWAY.