Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
Permit Number - T02OT00820
Inspection Description - SIGN ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/15/2002 | SIGN ELECTRIC | Approved | IVRS - Inspection 0000* | |
07/09/2002 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999*1.) FLEXIBLE CORDS NOT ALLOWED ABOVE CEILING. PLUG RECEPTACLE OUTLET FOR PORTABLE OPEN SIGN MUST BE RELOCATED TO BELOW CEILING. NEC 400-8. 2.) 1/2" FLEX CONDUIT CONTAINING PRIMARY WIRING NOT PROPERLY SECURED, NEC 350-18. 3.) JUNCTION OF ARMOURED CABLE WITH 1/2" CONDUIT NOT TERMINATED IN PROPER JUNCTION BOX NEC 300-15. | |
06/18/2002 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection 0000*WE BOY GOLD NEON ON RACEWAY. |