Permit: T02OT00795

Parcel: 132091020


Addresses:

3002 E RICKEY VISTA

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/29/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*CONDENSATE TERMINATION ANCHOR DISCONNECT & CONDUIT GAS VALVES ALL CORRECTIONS HAVE BEEN MADE OK FOR C OF O.
05/28/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*1.) CONTROL WIRING NEEDS TO BE PROTECTED IN APPROVED RACEWAY, EMT OR CONFLEX. 2.) GAS VALVE NEEDS TO BE WITHIN 3FT. OF UNIT. 3.) BLOCK/CLAMP HI VOLTAGE WIRING UP OFF OF ROOF AS NECESSARY. STABILIZE SWITCH ON ROOF AS NECESSARY KNOCK OUT RINGS ARE GOING TO POP 4.0 TERMINATE COND. DRAINS OVER WET VENT W/ 3/4" TEE.