Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/29/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*CONDENSATE TERMINATION ANCHOR DISCONNECT & CONDUIT GAS VALVES ALL CORRECTIONS HAVE BEEN MADE OK FOR C OF O. |
| 05/28/2002 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) CONTROL WIRING NEEDS TO BE PROTECTED IN APPROVED RACEWAY, EMT OR CONFLEX. 2.) GAS VALVE NEEDS TO BE WITHIN 3FT. OF UNIT. 3.) BLOCK/CLAMP HI VOLTAGE WIRING UP OFF OF ROOF AS NECESSARY. STABILIZE SWITCH ON ROOF AS NECESSARY KNOCK OUT RINGS ARE GOING TO POP 4.0 TERMINATE COND. DRAINS OVER WET VENT W/ 3/4" TEE. |