Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
Permit Number - T02OT00701
Inspection Description - SIGN ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/06/2002 | SIGN ELECTRIC | Approved | IVRS - Inspection 0000* | |
07/08/2002 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999*SIGN ELECTRIC DENIED 1.) NEC 600-5 PLEASE IDENTIFY BRANCH CIRCUIT SUPPLYING SIGN. 2.) NEC 350-18 FLEXIBLE CONDUIT EXCEEDING 3FT. IN LENGTH MUST BE SECURED WITHIN 12" OF EACH TERMINATION AND AT INTERVALS NOT TO EXCEED 4 1/2 FT. 3.)NEC 600-32 POWER PRO CABLE REQUIRES STRAIN RELIEF (SECURE THE CABLE AT TERMINAL END AND FOR EVERY 4' OF INTERMEDIATE LENGTH. SEE INSTALLATION INSTRUCTIONS 4.) NEC 370-28 JUNCTION BOX FOR PRIMARY WIRING REQUIRES A COVER. 5.) NEC 600-21 TRANSFORMERS MUST BE SECURELY MOUNTED IN PLACED. | |
07/01/2002 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999$COULD NOT LOCATE, NO UNIT # GIVEN FOR SIGN LOCATION NO SHOP INSPECTION DONE. |