Permit: T02OT00581

Parcel: 13612833A

Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Permit Number - T02OT00581

Inspection Description - SIGN ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
05/30/2002 SIGN ELECTRIC Approved IVRS - Inspection 0000*
05/28/2002 SIGN ELECTRIC Denied IVRS - Inspection 0999*REINSPECTION FEE APPLIED. 1.) NEC 350-18 SEE PREVIOUS NOTES 2.) NEC 334-10 SEE PREVIOUS NOTES. 3.) NEC 600-32E LOOK INSIDE TRANFORMER CANS. 4.) A REINSPECTION FEE HAS BEEN APPLIED TO THIS ACTIVITY. YOU MAY PAY FEE @ 201 N STONE. IN THE DSD OFFICES. REASON FOR RE-FEE IS THAT CORRECTION LISTED ON 5-20 WERE NOT MADE BEFORE CALLING FOR RE-INSPECT.
05/20/2002 SIGN ELECTRIC Denied IVRS - Inspection 0999* 1.) NEC 350-18 SUPPORT FLEX CONDUIT WITHIN 12" OF EACH TERMINATION AND AT INTERVALS NOT TO EXCEED 4 1/2'. LENGTHS OF FLEX CONDUIT LESS THAN 3' LONG DO NOT NEED TO BE SUPPORTED. 2.) NEC 334-10 MC CABLE TO BE SUPPORTED WITHIN 12" OF EACH TERMINATION AND @ INTERVALS NOT TO EXCEED 6'. 3.) NEC 600-9 DRAIN HOLES REQUIRED IN OPEN SIGNS UNLESS YOU PROVIDE LISTING FOR WATER TIGHT SIGN.
05/13/2002 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection 0000*
05/08/2002 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection 0000*NOT READY PIZZA HUT 3 LOGOS 2 "OPEN" SIGNS FLOURESCENT