Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
Permit Number - T02OT00530
Inspection Description - SIGN ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/14/2002 | SIGN ELECTRIC | Approved | IVRS - Inspection 0000* | |
05/06/2002 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999*1.) NEC 350-18 SUPPORT FLEXIBLE METAL CONDUIT WITHIN 12" OF EACH TERMINATION AND @ INTERVALS NO GREATER THAN 4 1/2. 2.) NEC 300-11 JUNCTION BOXES MUST BE SECURELY FASTENED IN PLACE. 3.) NEC 350-20 FITTING @ SWITCH BOX NOT INSTALLED PER LISTING (FLEX CONDUIT NIPPLE UNATTACHED). | |
04/29/2002 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection 0000*SIGN E. NOT READY. 1.) CHILDREN REACHING FOR SKY. 2 1/2' X 12' " FLOURSCENT. |