Addresses:

2108 W GRANT RD


Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Permit Number - T02OT00236

Inspection Description - SIGN ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
02/22/2002 SIGN ELECTRIC Approved IVRS - Inspection 0000*
02/21/2002 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection 0000*1.) GTO SCRAPING ON UNPROTECTED KNOCKOUT 300-16B 2.) GTO MUST BE MIN 1 1/2" FROM METAL 600-32E.