| 02/22/2002 |
SIGN ELECTRIC |
|
Approved |
IVRS - Inspection 0000* |
| 02/21/2002 |
SIGN ELECTRIC |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.) GTO SCRAPING ON UNPROTECTED KNOCKOUT 300-16B 2.) GTO MUST BE MIN 1 1/2" FROM METAL 600-32E. |