Permit: T02ME00778

Parcel: 133331030

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T02ME00778

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/11/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*ALL CORRECTION HAVE BEEN MADE.
12/10/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*NO CORRECTION MADE.
12/09/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*CONDENSATE CANNOT DRIP OVER THE EDGE OF THE ROOF. MUST GO TO WITHIN 6" OF THE GROUND. RECALL FOR INSPECTION.
11/27/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*
1.) USE A CHASE NIPPLE OR BUSHING WHERE ELEC. WIRES PENETRATE CABINET OF A/C UNIT.
2.) #8 WIRE NOT ADEQUATE FOR 60 AMP CIRCUIT FROM ELEC. DISCONNECT TO AC EQUIPMENT
3.) CONDENSATE CANNOT TERMINATE INTO A SEWER WASTE VENT GO TO THE GROUND. BLOCK & CLAMP PVC EVERY 4'. PAINT EXPOSED PVC W/LATEX.
4.) LABEL THE UNIT DATA PLATE W/PROPER HEAT KIT INSTALLED & FUSE UNIT ACCORDINGLY RECALL FOR INSPECTION.