Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T02ME00778
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/11/2002 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*ALL CORRECTION HAVE BEEN MADE. | |
12/10/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*NO CORRECTION MADE. | |
12/09/2002 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*CONDENSATE CANNOT DRIP OVER THE EDGE OF THE ROOF. MUST GO TO WITHIN 6" OF THE GROUND. RECALL FOR INSPECTION. | |
11/27/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* 1.) USE A CHASE NIPPLE OR BUSHING WHERE ELEC. WIRES PENETRATE CABINET OF A/C UNIT. 2.) #8 WIRE NOT ADEQUATE FOR 60 AMP CIRCUIT FROM ELEC. DISCONNECT TO AC EQUIPMENT 3.) CONDENSATE CANNOT TERMINATE INTO A SEWER WASTE VENT GO TO THE GROUND. BLOCK & CLAMP PVC EVERY 4'. PAINT EXPOSED PVC W/LATEX. 4.) LABEL THE UNIT DATA PLATE W/PROPER HEAT KIT INSTALLED & FUSE UNIT ACCORDINGLY RECALL FOR INSPECTION. |