Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/16/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
| 01/15/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/ 1) INSTALL PLASTIC BUSHING IN KNOCKOUT FOR A/C DISCONNECT 2) IMPROPER COLOR CODE (WHITE) FOR HOT LEAD IN A/C DISCONNECT. RED OR BLACK AND JUNCTION BOX 3) CLEANOUT PLUGGED WITH ILLEGAL KITCHEN WASTE LINE 4) KITCHEN WASTE VENT GREATER THAN 42" FROM TRAP 5) 714 ADDRESS MUST BE ON HOUSE 6) FILL OPEN KNOCK OUT IN OLD ELECTRIC PANEL 7) CLOTHES WASHER OUTLET MUST BE A DEDICATED OUTLET IN BATH OR GFCI PROTECTED 8) ADD BATTERY OPERATED SMOKE DETECTOR TO LIVING ROOM | |
| 01/02/2003 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*CONTINUE CONDENSATE PIPING TO WITHIN 6" OF GROUND. CAN'T DUMP OFF EDGE OF ROOF. PAINT PVC. |
|
| 12/24/2002 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*NEED TO PROVIDED PLASTER GROUND AT TAPS. SEAL ALL JOINTS W/ SLIP JOINTS BRING INTERNAL LINES DOWN TO TOP OF REGISTER. |