Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T02ME00766
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/03/2003 | MECHANICAL - FINAL | Approved | ||
12/04/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*USE A BUSHING OR CHASE NIPPLE WHERE ELEC. WIRES PENETRATE THE CABINET OF A/C UNIT. 2.) CONDENSATE DRAIN LINE RUNNING ACCROSS THE ROOF DOES NOT HAVE ADEQUATE SLOPE. PROVIDE MIN. 1/8" PER FT. SLOPE RECALL FOR INSPECTION. |